Model No.
|
MID 30KTL3-X2-1
|
MID 33KTL3-X2
|
MID 36KTL3-X2
|
MID 40KTL3-X2
|
MID 50KTL3-X2
|
|
Warranty
|
|
Product Warranty (Min)
|
5 Years
|
5 Years
|
5 Years
|
5 Years
|
5 Years
|
|
Input Data(DC)
|
|
Max. DC Power
|
45 kW
|
49.5 kW
|
54 kW
|
60 kW
|
75 kW
|
|
Max. DC Voltage
|
1100 V
|
1100 V
|
1100 V
|
1100 V
|
1100 V
|
|
Nominal DC Voltage
|
600 V
|
600 V
|
600 V
|
600 V
|
600 V
|
|
Min. DC Voltage to Start Feed In
|
200 V
|
200 V
|
200 V
|
200 V
|
200 V
|
|
Max. DC Current
|
96 A
|
96 A
|
96 A
|
128 A
|
128 A
|
|
MPP(T) Voltage Range
|
200~1000 V
|
200~1000 V
|
200~1000 V
|
200~1000 V
|
200~1000 V
|
|
No of MPP Trackers
|
|
DC Inputs
|
|
Output Data (AC)
|
|
Nominal AC Power
|
30 kW
|
33 kW
|
36 kW
|
40 kW
|
50 kW
|
|
Output AC Voltage Range
|
340~440 V
|
340~440 V
|
340~440 V
|
340~440 V
|
340~440 V
|
|
Max. AC Current
|
45.5 A
|
55.5 A
|
60.6 A
|
67.3 A
|
84.1 A
|
|
Frequency Range
|
45-65 Hz
|
45-65 Hz
|
45-65 Hz
|
45-65 Hz
|
45-65 Hz
|
|
Frequency
|
50, 60 Hz
|
50, 60 Hz
|
50, 60 Hz
|
50, 60 Hz
|
50, 60 Hz
|
|
Power Factor (cosθ)
|
|
Distortion (THD)
|
< 3 %
|
< 3 %
|
3 %
|
< 3 %
|
< 3 %
|
|
No of feed-in phases
|
|
Max. Efficiency
|
98.8 %
|
98.8 %
|
98.8 %
|
98.8 %
|
98.8 %
|
|
Euro Efficiency
|
98.5 %
|
98.5 %
|
98.5 %
|
98.5 %
|
98.5 %
|
|
General Data
|
|
Dimensions (H/W/D)
|
435x580x230 mm
|
435x580x230 mm
|
435x580x230 mm
|
435x580x230 mm
|
435x580x230 mm
|
|
Weight
|
31 kg
|
31 kg
|
31 kg
|
37 kg
|
37 kg
|
|
Power Consumption at Night
|
< 1 W
|
< 1 W
|
< 1 W
|
< 1 W
|
< 1 W
|
|
Operating Temperature
|
-25 ~ +60 ℃
|
Transformer
|
Transformerless
|
Protection Class
|
IP66
|
Humidity
|
0-100 %
|
Cooling
|
Fan
|
Max. Altitude
|
4000 m
|
Interface
|
RS 485, USB
|
Display
|
LED
|
Protection Features
|
|
Protection Features
|
Anti Island Protection(ENS), Short Circuit Protection, Residual Current Device (RCD), Reverse Polarity Protection, Surge Protection, Ground Fault Monitoring, Isolation Monitoring, Grid Monitoring
|
PDF
|
|